UPS5000-A-500 kVA
User Manual (e-shelter)
4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
110
Figure 4-40
Battery string configuration
Set the iBOX and iBAT number for each battery string.
4.1.2.4 Maintenance
On the
System Info
screen, tap
to display the
Maintenance
screen.
Figure 4-41
Maintenance 1
Battery Maintenance
Perform battery maintenance when no alarm is active on the UPS. Otherwise, the UPS
may supply no power.
A proportion of battery capacity will discharge during battery maintenance. This reduces
the discharge time before the next charge.
Do not perform battery maintenance when a D.G. is connected.