UPS5000-A-500 kVA
User Manual (e-shelter)
4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
111
Perform battery maintenance periodically to increase the battery lifespan and improve the
UPS reliability. Battery maintenance includes
Forced Equalized Charging
,
Shallow Dis.
Test
, and
Capacity Test
. The next maintenance time displayed on the screen indicates the
upcoming time in which to check batteries.
Figure 4-42
Battery maintenance
Item
Description
Forced Equalized Charging
Forcibly perform equalized charging on batteries.
Shallow Dis. Test
Partially discharge batteries. A shallow discharge test can
be conducted to test the battery loop reliability and short-
time discharge capacity when the batteries have not
discharged for a long time.
Capacity Test
Fully discharge batteries. A deep discharge test is
conducted to obtain the battery discharge performance
data.
USB Operations
Figure 4-43
USB operations 1