UPS5000-A-500 kVA
User Manual (e-shelter)
4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
113
Item
Description
Blink
Make the red indicator on the iBAT start or stop blinking super fast.
Internal
resistance
Measure the battery internal resistance. If the condition for measuring
internal resistance is met (batteries are fully charged), you can tap
Measure
to start measuring the internal resistance of the selected iBAT in
an iBOX.
NOTE
The interval between two measurement operations must be greater than 10 minutes.
4.1.2.5 About Screen
On the
About
screen, you can view the model, manufacturer, monitoring version, and power
version. To view version details, tap
Version Info
.
Figure 4-45
About screen
4.1.3 System Status
On the
System Status
to view the mains input, bypass input, load, and battery information.