UPS5000-A-500 kVA
User Manual (e-shelter)
5 Operations
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
138
Figure 5-1
Settings Wizard
Set the time and date correctly. Incorrect time and date will cause false fault analysis during
maintenance or repair.
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.
Table 5-2
Battery parameter setting example
Battery
Specifications
Number of
Batteries
Number of
Battery
Strings
Number of
Cells
Battery
Capacity
150 Ah/12 V
36 batteries in
series
Two battery
strings
connected in
parallel
36 x 6 = 216
150 Ah + 150
Ah = 300 Ah
300 Ah/2 V
192 batteries in
series
Two battery
strings
connected in
192 x 1 = 192
300 Ah + 300
Ah = 600 Ah