5 Operations
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
145
Step 5
On the home page of the WebUI, choose
Monitoring
>
Control
, click
Inv. ON
, and confirm
the operation to start the inverter.
Figure 5-9
Starting the inverter
If the power unit receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the unit, or you perform shutdown or rectify faults) and the unit can be started, the unit responds to
the startup command.
----End
5.1.3 Powering On Loads
Context
After the inverter starts, the UPS works in normal mode. The
Bypass mode
alarm disappears.
Procedure
Step 1
After confirming that the battery strings are properly connected, close the battery string input
circuit breaker. If there are multiple battery strings, close the circuit breaker for each battery
string and then the general circuit breaker between battery strings and the UPS. The
No
battery
alarm disappears from the MDU.
Step 2
Close the UPS downstream output switch to supply power to the loads.
----End
5.1.4 (Optional) Setting Parameters for the BCB Box
Prerequisites
A BCB box is installed.
Procedure
Step 1
On the
Settings
>
Dry Contact Set
screen, set
MUE05A connection
to
Enable
, and set
BCB
connection [OL]
and
Battery breaker [STA]
to
Enable
.