UPS5000-A-500 kVA
User Manual (e-shelter)
8 Technical Specifications
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
165
8
Technical Specifications
Table 8-1
Physical Parameters
Physical
Parameters
500 kVA
Cabling mode
Cables are routed from the top or bottom.
Protection level
IP20 (IP21 can be reached by configuring IP21 components.)
Dimensions (H x W
x D)
2000 mm x 1200 mm x 850 mm
Communication
Supports dry contacts, RS485 ports, and FE ports. Supports Simple
Network Management Protocol (SNMP).
Weight
810 kg
Table 8-2
Internal Switch Parameters
Maintenance bypass switch
1000 V AC/800 A/3P
Table 8-3
Environment Parameters
Environment Feature Parameters
Operating temperature
0–40°C
Storage temperature
–40°C to +70°C
Relative humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
When the altitude is greater than 1000 m and less than 4000 m,
the rated power should be derated. For details, see the
IEC62040-3.