UPS5000-A-500 kVA
User Manual (e-shelter)
8 Technical Specifications
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
166
Table 8-4
Safety Regulations and EMC
Item
Parameters
Safety regulations
EN62040-1
EMC
EN62040-2
IEC62040-2
IEC61000-2-2
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
EN61000-4-3
EN61000-4-6
IEC61000-4-8
IEC61000-4-11
Table 8-5
Mains Input Electrical Specifications
Item
Parameters
Input system
Three-phase, four-wire, and PE.
Rated input voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input voltage
80–280 V AC (phase voltage)
At 0–40°C: The UPS works at full load when the voltage
is 176–280 V AC. The load bearing capacity is derated to
40% when the voltage is 176–80 V AC.
Rated frequency
50 Hz or 60 Hz
Input frequency
40–70 Hz
Input PF
> 0.99 (full load)
> 0.98 (half load)
THDi
THDi ≤ 3% (full linear load)
THDi ≤ 5% (full non-linear load)
Table 8-6
Bypass Input Electrical Specifications
Item
Parameters
Input system
Three-phase, four-wire, and PE