Item
Parameters
Frequency
In normal mode, the mains frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance
±0.05%).
Total harmonic
distortion of
output voltage
(THDv)
THDv ≤ 1% at rated input voltage and 100% linear load
THDv ≤ 4% at rated input voltage and 100% non-linear load
Output PF
1
Transfer time
0 ms (uninterruptible transfer)
≤ 20 ms (interruptible transfer)
Output voltage
unbalance
Voltage unbalance: ±3%; phase unbalance: 120±2°
Overload
capability
Inverter overload capability:
100% < load ≤ 110%: transfer to bypass mode after 60 min
110% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
Load > 150%: transfer to bypass mode after 200 ms
Bypass overload capability:
At 30°C, load ≤ 135%: long-time operation
At 40°C, load ≤ 125%: long-time operation
load > 1000% : run for 100 ms
Table 8-9
System Electrical Specifications
Item
Parameters
Redundancy design
The auxiliary power supplies, centralized
controllers, and parallel signals use redundancy
design.
ECO
Supported