UPS5000-A-500 kVA
User Manual (e-shelter)
A Alarm List
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
175
Alarm ID
(Alarm ID-
Cause ID)
Alarm Name
Severity
Cause
Solution
0085-1
EPO
Critical
The EPO button is pressed.
Restore the EPO button
status. Start the UPS after the
alarm is cleared.
0086-1
Max. number
of BPM
transfers
Minor
The system frequently
transfers to bypass mode
due to overload timeout or
load impact.
Check the load.
0087-1
System
transfer-to-
bypass
Warning
The neighboring UPS is
not normal, and transfers to
bypass mode.
Check the reason why the
neighboring UPS transfers to
bypass mode.
0089-1
Rack output
overload
Minor
The load is excessive.
Check the load. Remove
some loads or expand the
UPS power capacity if the
UPS is overloaded.
0090-1
Dry contact
board fault
Critical
I2C communication with
the dry contact board
MUE05A fails.
Replace the dry contact
board MUE05A.
0090-2
I2C communication with
the dry contact board
MUE06A fails.
Replace the dry contact
board MUE06A.
0356
Battery Mode
Minor
The UPS is working in
battery mode.
The running status is
displayed. See details about
how to handle other alarms.
0359
No power
supplied
Warning
No power is supplied.
The running status is
displayed. See details about
how to handle other alarms.
0332
Output disabled Minor
The output is disabled.
The running status is
displayed. See details about
how to handle other alarms.
0334
BSC master
system
Warning
BSC master system.
The running status is
displayed. No further
measures are required.
0334
BSC slave
system
Warning
BSC slave system.
The running status is
displayed. No further
measures are required.
0342
Mains input
breaker open
Critical
The mains input circuit
breaker is OFF.
The running status is
displayed. No further
measures are required.
0343
BPM input
breaker open
Critical
The bypass input circuit
breaker is OFF.
The running status is
displayed. No further
measures are required.