UPS5000-A-500 kVA
User Manual (e-shelter)
3 Installation
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
40
Figure 3-3
Removing the pallet from the UPS
----End
3.1.5 (Optional) Splitting the Power Cabinet and Bypass Cabinet
Context
If the door of the power distribution equipment room is not wide enough to move the UPS,
you can split the power cabinet and bypass cabinet before the movement.
Put away the removed screws and connecting kits and take photos to record removed
positions to facilitate later cabinet combination.
Table 3-5
Screw specifications and quantity
Position
Screw Specifications
Quantity (PCS)
Soft copper bar
M12x35
26
Battery copper bar
component
M8x20
4
Top connecting kit
M6x30
8
Middle connecting kit
M6x30
8
Bottom connecting kit
M12x35
8