UPS5000-A-500 kVA
User Manual (e-shelter)
3 Installation
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
45
Figure 3-8
Removing connecting kits
Step 8
Use a manual pallet truck to transport the power cabinet and bypass cabinet to the installation
position. Ensure that the two cabinets align with each other.
----End
3.1.6 (Optional) Combining the Power Cabinet and Bypass
Cabinet
Procedure
Step 1
Reinstall the bottom, middle, and top connecting kits for the power cabinet and bypass cabinet
based on screw specifications, screw quantity, and recorded information.
Step 2
Reinstall the removed soft copper bars and battery copper bar components based on their
numbers, screw specifications, screw quantity, and recorded information.
Step 3
Reconnect the removed cables to the system signal interface board in the power cabinet, and
bind the cables based on the recorded information.
Step 4
Check that the power cabinet and bypass cabinet are combined completely and securely.
Step 5
After checking that cabinets are combined properly, reinstall the side covers and rear covers.
----End