3.2.2 Installing the UPS on Channel Steel
Context
Channel steel and expansion bolts for securing the channel steel should be purchased by
the customer. The recommended channel steel width is 50 mm or more.
Ensure that the spacing between external sides of a channel steel is 800 mm. Secure
channel steel to the ground by using expansion bolts.
Keep the channel steel surface flat.
Procedure
Step 1
Determine the cabinet installation positions on the channel steel based on holes in the
marking-off template for channel steel installation.
A: mounting holes on the channel steel
B: mounting holes on the floor
Figure 3-14
Hole dimensions (unit: mm)
Step 2
Drill cabinet mounting holes in channel steel by using a hammer drill.
Step 3
Use a pallet truck to move the cabinet to the installation position.
Step 4
Use common M12x45 bolts to secure the cabinets into the mounting holes in the channel steel
and tighten the bolts.