UPS5000-A-500 kVA
User Manual (e-shelter)
3 Installation
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
61
Figure 3-27
Connecting the bypass input power cables
Step 9
Connect the battery cables.
The battery voltage may result in serious injury. Observe safety precautions when
connecting cables.
Ensure that cables are correctly connected between battery strings and the battery switch,
and between the battery switch and the UPS. Avoid inverse connections.