UPS5000-A-500 kVA
User Manual (e-shelter)
4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
86
After you restart the device,
IP address allocation
changes back to
Manual
. The IP address is set to the
IP address set previously.
Item
Description
IP address
Set an Ethernet IP address that ranges from 1.0.0.0 to
223.255.255.255. The default value is
192.168.0.10
.
NOTICE
Ensure that the UPS IP address is unique on the network segment. Otherwise,
the WebUI display function may not function properly.
Subnet mask
Set an Ethernet subnet mask that ranges from 0.0.0.0 to
255.255.255.255. The default value is
255.255.255.0
.
Gateway
Set an Ethernet gateway that ranges from 1.0.0.0 to 223.255.255.255.
The default value is
192.168.0.1
.
NAT mapping
NAT means network address translation. If it is set to
Disable
,
Internet cannot access IP addresses in the local area network (LAN).
The default value is
Disable
.
RS485
address/RS485
baud rate
Set an address that ranges from 1 to 254 for this port.
RS485 baud
rate
depends on the network management conditions.
The default values of
RS485 address
and
RS485 baud rate
are
1
and
9600
respectively.
Figure 4-14
Communication screen 2
Item
Description
RS485
Parity
mode
Verify the validity of RS485 communication characters. When a device
node adopts RS485 communication, ensure that the parity modes for the
device nodes are set to the same mode. Available parity modes include
None
,
Odd
, and
Even
.