UPS5000-A-500 kVA
User Manual (e-shelter)
4 User Interface
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
88
Item
Description
WiFi SSID
When using the mobile app for site setup or inspection, set WiFi SSID
after connecting a WiFi module over a USB port to identify the WiFi
device to which the mobile phone is connected.
WiFi Password
The password for accessing WiFi.
Basic Parameters
Parameter settings must meet the actual values. Otherwise, alarms will be generated or serious
faults may occur.
Set basic system and battery parameters, as shown in
Figure 4-16
Basic parameters
Item
Description
Single/Parallel
The value for the UPS running mode can be
Single
(default) or
Parallel
.
Output voltage
level
Indicates the system output voltage level. This parameter is
configurable only after the inverter shuts down. For three-phase
output, this parameter can be set to 380 V, 400 V (default), or 415
V. After you change the voltage level, the upper limit of the bypass
voltage restores to the default value. (If the voltage level is 380 V or
400 V, the default upper limit is +15%. If the voltage level is 415
V, the default upper limit is +10%.)
Output frequency
(Hz)
The value for the system output frequency can be 50 Hz (default) or
60 Hz.
Battery capacity
The value range is 5 Ah to 9999 Ah. 600 Ah is set by default for the