b) After you set parameters on the 

Settings Wizard

screen, the MDU displays the 

Bypass mode

and 

No battery

alarms, which  do not need  to be handled.  If there is any other alarm, you need 

to rectify the fault. 

c) View the system running  status diagram on the MDU to check  that the UPS  is working in 

bypass mode. 

d) Start the inverter on the app.

• The 

Service  Expert

app can be downloaded  from Google Play and can run  on Android.

• The port number is 

443

by default and can be modified. If the UPS is managed using the app, 

the port number  must be set to 

443

.

NOTE

Download  the mobile phone  app (Service Expert).

On the app home  screen, tap 

StartUp

to 

access the 

Set Startup 

screen. Set the 

Site

and 

Device  Type

as required, and  connect 

the device. Enter the UPS 

IP

and 

Port

as well 

as the user name  and  password of the WebUI

account,  and tap 

Login

.

Enable  the mobile  phone  WLAN, search for 
the UPS  WiFi signal,  and connect  to the  WiFi

signal. The default value of 

SSID

is 

UPS_WIFI

.

Insert the WiFi module  into the USB  port on 

the MDU. Set 

System Info 

Settings

Comm Settings

WiFi Settings 

on the MDU. 

The initial  WiFi password is 

Changeme

by 

default.

After login,  tap 

Power-on password 

activation

on the screen. A message is 

displayed, indicating  whether to start the UPS. 

Tap 

OK

.

Enter 

Bar code

and 

Verification code

obtained  from the MDU on  the 

Offline 

Activation

screen. Tap 

Generate PWD

to 

generate a startup password.

On the MDU, choose 

System  Info 

Maintenance

Inv. ON 

and  obtain the 

Bar 

code 

and 

Verification

.

Enter the generated  password in the 

password textbox on the MDU to start the 

inverter.

Use the app to 

start the inverter 

online?

Yes

No, start the 
inverter 
offline

Open the 

Service Expert

app on the mobile 

phone.

Open the 

Service Expert

app on the mobile 

phone.

On the home  screen of the app, tap 

StartUp

to access the 

Set Startup

screen. Set 

Site

and 

Device  Type

as required, and  tap 

Offline Activation

.

Non-initial Startup

a. Choose 

Common  Functions 

from the main  menu  and tap 

Inv. ON

.

b. In the displayed  login  window, enter the user name  and password, and tap          .
c. In the displayed  dialog box, tap 

OK

to start the inverter.

To ensure  system security, change  the LCD 
and WebUI passwords after the first login.

NOTE

Summary of Contents for UPS5000-A-800 Series

Page 1: ...nfiguration Full configuration Weight 1530 kg 1610 kg Dimensions H x W x D 2000 mm x 2400 mm x 850 mm 1 Power unit 2 Control unit 3 Mains input switch only available in the full configuration model 4 Maintenance bypass switch 5 Output switch only available in the full configuration model 6 Bypass unit 7 Bypass input switch only available in the full configuration model Power cabinet Bypass cabinet...

Page 2: ...ment damage may occur and the UPS faults caused are beyond the warranty scope of Huawei Install on the steel channel or floor Determine the mounting hole positions unit mm using a marking off template drill holes and install expansion sleeves based on site requirements A mounting holes on the steel channel B mounting holes on the floor 2 Installing the UPS Determining Installation Position 2 1 Com...

Page 3: ...ts B Mounting holes on the floor M12x100 expansion bolts 2 Secure the UPS 4 Remove the front cover and No 10 protection panel from the bypass cabinet and the filler panel from the power cabinet 3 Install anchor baffle plates Bolts are not included NOTE ...

Page 4: ...n there are two mains inputs 2 In the case of single mains you do not need to connect bypass input power cables and remove short circuit copper bars UPS Cable Connection Reference Prepare cables away from the cabinets to prevent scraps from falling inside Cable scraps may ignite and cause personal injury or device damage After cables have been installed clean the cabinets in a timely manner Keep t...

Page 5: ...uration has only one switch cable maintenance bypass switch A UPS in full configuration has three switch cables mains input switch maintenance bypass switch and bypass input switch The following figure shows how to connect cables to a UPS in full configuration Connecting Signal Cables to Combined Cabinets 3 2 NOTE ...

Page 6: ...onfiguration 04091625 06 Standard configuration SW1310 04091626 23 1 Remove the covers from the top of the cabinet drill holes in the covers for the power cables and battery cables attach grommet strips to the hole edges to protect the cables and reinstall the covers Connecting Power Cables and Signal Cables 3 3 Scenario 1 Routing Cables fromthe Top A Signal cable hole B Battery cable hole C Power...

Page 7: ...rp exercise caution when removing the connecting copper bars to prevent personal injury Port Bolt Specifications Torque Mains input M16x50 120 N m Bypass input M16x50 120 N m Battery input M16x50 120 N m Output M16x50 120 N m PE M12x35 47 N m NOTE Ground cable The wire routed from the middle point between positive and negative battery strings is the neutral wire Take a battery string consisting of...

Page 8: ... covers Output power cable Mains input power cable Ground cable Signal cable Battery cable The mains input and bypass input share the N busbar 2 Skip this step if the mains input and bypass input share a power source Remove the copper bars between the mains input and bypass input 3 Connect the ground cable power cables and signal cable Bypass input power cable no need to connect in case of only on...

Page 9: ... and the cabinet using sealing putty Dustproof cover 4 Do not remove the dustproof cover before power on to prevent dust inside the UPS Sealing putty Sealing putty must be used as a whole and the gap can be sealed only from the top Paper protective film 5 Powering On and Starting the UPS 1 Before powering on the UPS ensure that the UPS has passed all check items in the UPS5000 Commissioning and Ac...

Page 10: ... on initialization begins The MDU displays the Huawei logo and an initialization progress bar Starting the Inverter 5 2 System User LCD Preset Password WebUI Preset Password admin system administrator 000001 Changeme operator common user 000001 Changeme Initial Startup a If this is the initial startup set the language time date network parameters and system parameters on the Settings Wizard screen...

Page 11: ...e USB port on the MDU Set System Info Settings Comm Settings WiFi Settings on the MDU The initial WiFi password is Changeme by default After login tap Power on password activation on the screen A message is displayed indicating whether to start the UPS Tap OK Enter Bar code and Verification code obtained from the MDU on the Offline Activation screen Tap Generate PWD to generate a startup password ...

Page 12: ...rom the MDU 2 After confirming that the battery strings are properly connected turn on the battery string input circuit breaker If there are multiple battery strings turn on the circuit breaker for each battery string and then turn on the general circuit breaker between battery strings and the UPS The No battery alarm disappears from the MDU 3 Turn on the UPS downstream output switch to supply pow...

Page 13: ...l the switch extension rod Keep the dowel level insert the switch extension rod to the marked position place washers properly and tighten the slotted screw to install the switch extension rod NOTE Huawei Technologies Co Ltd Huawei Industrial Base Bantian Longgang Shenzhen 518129 People s Republic of China www huawei com ...

Reviews: