UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
4 User Interface
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
107
Item
Description
Default Value Value Range
bypass voltage is not normal and
that the bypass is unavailable.
the value range is +10%, +15%,
and +20%. The default value is
+15%.
When the voltage level is 415 V,
the value range is +10% and
+15%. The default value is
+10%.
Minimum
bypass voltage
When the difference between the
bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
–20%
–10%, –15%,
–20%, –30%,
–40%, –50%,
–60%
Bypass
frequency
range (Hz)
When the difference between the
bypass input frequency and the
rated frequency is greater than
the specified value, the system
determines that the bypass
frequency is abnormal, so the
bypass is unavailable.
±2 Hz
±0.5 Hz to ±6
Hz
Battery Settings
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following: