UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
4 User Interface
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
109
Figure 4-29
Battery settings 3
Item
Description
Default Value Value Range
Battery type
Currently, only
VRLA batt.
is
supported.
N/A
N/A
Single battery
voltage (V)
Specifies the voltage of each
battery that is connected in the
battery string in series.
12 V
2, 6, 12
Single battery
capacity (Ah)
Specifies the capacity of each
battery that is connected in the
battery string in series.
Depends on the
actual model.
5–9999
Batteries in a
battery string
Specifies the number of batteries
in a battery string.
The default
value depends
on the model.
The value range
depends on the
model.
Number of
battery strings
Specifies the number of battery
strings connected in parallel.
1
1–4
Installation
time
A battery maintenance reminder
is displayed when the
maintenance time (counted from
the installation time) comes.
N/A
N/A
Maintenance
period (d)
Specifies the interval for
reminding users of battery
maintenance.
0
0–365
Chg. cur.
limiting coef.
(C)
The charging current limit is a
multiple of the battery capacity.
0.10
0.05 to 0.15
Cell float
voltage (V/cell)
Specifies the battery float
charging voltage.
2.25 V/cell
2.23 V/cell to
2.30 V/cell
Cell equalized
volt. (V/cell)
Specifies the battery equalized
charging voltage.
2.35 V/cell
2.30 V/cell to
2.40 V/cell
Dis. cur. 0.1C
EOD (V/cell)
Specifies the EOD threshold
when the discharging current is
1.80 V/cell
1.8–1.9