UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
4 User Interface
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
110
Item
Description
Default Value Value Range
Dis. cur. 0.3C
EOD (V/cell)
0.1C, 0.3C, 0.5C, and 1.0C
respectively.
1.80 V/cell
1.8–1.9
Dis. cur. 0.5C
EOD (V/cell)
1.75 V/cell
1.75–1.85
Dis. cur. 1.0C
EOD (V/cell)
1.60 V/cell
1.6–1.75
Sched. shallow
dis. test
When certain conditions are met,
the charger shuts down, and
batteries supply power to loads.
The system records the battery
discharge data as the reference
for battery capacity and lifespan.
Disable
Disable, Enable
Sched. shallow
dis. test time
Time for scheduled shallow
discharge test.
00:00 - 06:00
00:00 - 06:00,
06:00 - 12:00,
12:00 - 18:00,
18:00 - 24:00
Sched. shallow
dis. test interval
(d)
Interval for scheduled shallow
discharge test.
60
30–90
Shallow dis.
test dis. ratio
(%)
Set the proportion of the
discharge capacity to the total
discharge capacity. The value is
configurable in any mode.
20
10–50
iBOX Settings
Figure 4-30
iBOX Settings
On the
System Info
>
Settings
>
iBOX Settings
>
Basic Param.
screen, if the
Number of iBOXs
is
not
0
the
Batt. String Config
is displayed on the
iBOX Settings
screen.