UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
4 User Interface
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
130
Item
Description
Default Value Value Range
warning thresh.
(min)
Remain. cap.
warning
An alarm is generated if this
parameter is set to
Enable
and
the remaining capacity is less
than the warning threshold.
Disable
Disable, Enable
Remain. cap.
warn. thresh.
(%)
Remaining capacity warning
threshold
20
5–50
Intelligent
hibernation
If this parameter is set to
Enable
,
the intelligent battery hibernation
function is enabled.
Disable
Disable, Enable
Class 1 grid
hiber. time (d)
Hibernation time for class 1
power grids.
13
0–30
Class 2 grid
hiber. time (d)
Hibernation time for class 2
power grids.
6
0–15
Thres. of low
batt. SOC over
dry contact (%)
If an output dry contact is set to
Low battery SOC
, and the
battery SOC is lower than this
threshold, the output dry contact
will output signals.
75
5–80
Thres. of low
batt. volt. over
dry contact
(V/cell)
If an output dry contact is set to
Batt. Volt. Below Threshold
,
and the battery voltage is lower
than this threshold, the output dry
contact will output signals.
1.70
1.70–2.10
Battery String Summary
Item
Description
No. of iBOX
Number of an iBOX connected to the UPS.
iBAT start No.
Start number of an iBAT connected to the iBOX.
iBAT end No.
End number of an iBAT connected to the iBOX.
4.2.3 Query
On the
Query
page, you can query
Historical Alarm
,
Battery Test Record
s, and
Performance Data
, and perform
Export Data
.