UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
5 Operations
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
142
If you need to shut down the inverter and transfer the UPS to bypass mode, check that the UPS has not
generated an alarm and perform "Step 1".
On the WebUI
Choose
Monitoring
>
UPS System > Running Control
, and click
Inv. OFF
.
Step 2
After shutting down the inverter, open the output switch, or external output power distribution
switch in the UPS output PDC.
Step 3
Open the battery string switch. If there are multiple battery strings, open the general switch
between battery strings and the UPS and then the switch for each battery string.
Step 4
Open the external input power distribution switch and the UPS internal switch, perform the
following operations:
1.
Open the internal mains input switch, bypass input switch, output switch.
2.
Open the upstream UPS mains and bypass input switches.
If the inverter needs to shut down to transfer the UPS to bypass mode, check that the UPS has not
generated an alarm and perform
If you need to shut down the UPS, perform all of the preceding steps.
----End
5.3 Starting the UPS in Battery Mode
Procedure
Step 1
Ensure that batteries have been connected properly. Use a multimeter to check that the
absolute voltages of positive and negative battery strings are greater than a certain value
(single battery voltage x number of batteries in the battery string).
Step 2
Open the upstream mains input and bypass input switches, and close the battery circuit
breaker. If there are multiple battery strings, close the circuit breaker for each battery string
and then the general circuit breaker between battery strings and the UPS.
Step 3
Use a multimeter to measure the positive and negative battery string voltages at the UPS
battery input terminal. If the absolute values of the voltages are greater than a certain value
(single battery voltage x number of batteries in the battery string), the batteries are connected
properly.
Step 4
Press and hold down the
BATT START
button on the bypass module for at least 2 seconds.
The system automatically enters the battery cold start status. The LCD displays the Huawei
logo and an initialization progress bar.
Step 5
After LCD initialization, start the inverter on the LCD.
----End