UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
5 Operations
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
152
E-Label
Fault Information
This topic describes how to export historical alarms.
Web
1.
Choose
Query > Export Data > Export Historical Data
. Set
Encryption Password
for Export
, and select
Historical Alarm
from the
Data Type
drop-down list.
Figure 5-16
Export Historical Data
2.
Click
Export Historical Data
and save the displayed webpage.
5.12 Setting Hibernation Mode
When the load power is small and stable, you can shut down the inverters in some power
modules so that these power modules enter hibernation mode and other power modules bear
all the load power. This improves the system efficiency in the case of small load power and
increases the power module service life. The hibernation function can be set on the WebUI.
Ensure that the load power is stable. If the system load power fluctuation is greater than
the rated capacity of half a module (for example, the single-phase load power fluctuation
is greater than 5 kVA for a 30 kVA module), the UPS may enter and exit from hibernation
mode repeatedly.
Check that the number of redundant power modules and racks are appropriate. If the
number is insufficient, the UPS may not enter hibernation mode.
Web
1.
On the WebUI, choose
Monitoring
>
UPS system
>
Running Parameter
and set
Paral
sys hibernate
to
Enable
.
2.
Set the module cycle hibernation period to an integer ranging from 1 to 100. The default
value is 30.