UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
B Alarm List
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
171
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
0530-1
Battery ground fault Critical
The battery
string is not
properly
grounded.
The battery
ground
monitoring cable
is faulty.
The dry contact
board is faulty.
1.
Check whether the positive
and negative terminals of the
battery string are grounded or
have sufficient resistance to
the ground.
2.
Check whether the battery
grounding failure detector is
faulty by replacing it with a
new one.
3.
If no battery grounding failure
detector is available, check on
the dry contact board whether
the battery grounding failure
detector is enabled. If yes,
disable it and check whether
the alarm is cleared. If the
alarm persists, the dry contact
board may be faulty. Replace
the board.
0032-1
Battery overvoltage
protection
Critical
The battery
voltage is greater
than the upper
threshold.
The configured
number of
batteries is less
than the actual
number.
The actual
number of
batteries does not
meet
requirements.
1.
Check the battery voltage.
2.
Check that the configured
number of batteries matches
the actual number.
3.
Check that the actual number
of batteries meets
requirements.
0036-2
Battery
maintenance
reminder
Warning
The time for
maintenance arrives.
Maintain the batteries.
0037-1
Battery
undervoltage
Critical
The UPS has
worked in battery
mode for an
extended amount
of time.
The charger is
faulty.
1.
Check whether the battery
voltage is normal.
2.
Check whether the output is
overloaded.
3.
Check whether any battery is
damaged. If yes, replace the
battery.
4.
Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.