UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
B Alarm List
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
174
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
upper threshold.
The load is
excessive.
0583-1
Inter-rack par. cable
abnormal
Critical
The inter-rack
parallel system
CAN bus is
disconnected or
short-circuited.
Only one rack
works in a
parallel system.
An ECM is
faulty.
1.
Check the inter-rack parallel
system CAN bus.
2.
Rectify the disconnection or
short-circuit fault.
3.
Replace the ECM.
0583-4
The inter-rack
industrial frequency
synchronization
cable is broken.
Replace the inter-rack parallel
cable.
0583-5
The inter-rack
carrier
synchronization
cable is broken.
0583-6
The intra-rack
INVBYP cable is
broken.
The parallel
CAN bus is
broken.
0584-2
Inter-rack par. cable
alarm
Minor
The inter-rack
parallel cable is
faulty.
Replace the inter-rack parallel
cable.
0584-4
The inter-rack
industrial frequency
synchronization
cable is broken.
0085-1
EPO
Critical
The EPO button is
pressed.
Restore the EPO button status.
Start the UPS after the alarm is
cleared.
0086-1
Max. number of
BPM transfers
Minor
The system
frequently transfers
to bypass mode due
to overload timeout
or load impact.
Check the load.