UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
2 Overview
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
23
2.3.2 Power Module
Appearance
Figure 2-9
Power module
(1) Positioning lock
(2) Run indicator
(3) Alarm indicator
(4) Fault indicator
(5) Ready switch
(6) Output port
(7) Input port
Functions
The power module consists of a PFC rectifier and inverter. The power module performs
AC-DC or DC-DC conversion on the mains and battery inputs, and stabilizes the bus voltage.
The inverter converts DC inputs into AC sine wave outputs.
Specifications
Dimensions (H x W x D): 86 mm x 442 mm x 620 mm
Weight: < 21 kg
Rated output capacity: 30 kVA/30 kW
Power density: 20.64 W/inch
3