UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
2 Overview
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
25
Indicator
Color
Status
Description
0.125s).
Off
The bypass software is being
upgraded.
Alarm indicator
Yellow
Steady on
A minor alarm is generated
for the bypass.
Off
There is no minor alarm for
the bypass, or the software is
being upgraded.
Fault indicator
Red
Steady on
A critical alarm is generated
for the bypass.
Off
There is no critical alarm for
the bypass, or the software is
being upgraded.
Functions
The bypass module supplies power in the following cases:
If the UPS is set to ECO mode and the bypass voltage is within the specified range, the UPS
works in bypass mode.
If the power module overload times out, the UPS transfers to bypass mode.
Both the active and standby ECMs are abnormal.
The system fails to run properly and transfers to bypass mode.
A manual operation is performed to transfer to bypass mode.
Specifications
Dimensions (H x W x D): 130 mm x 420 mm x 500 mm
Weight: 19 kg
Rated output capacity: 200 kVA