UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
3 Installation
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
47
Item
Specifications
30 kVA
60 kVA
90 kVA
120 kVA
N
Bypass
input
Bypass input current (A)
45
91
136
182
Recommended
cross-sectional
area (mm
2
)
L1
4 x 10
4 x 25
4 x 50
4 x 70
L2
L3
N
Output
Output current (A)
45
91
136
182
Recommended
cross-sectional
area (mm
2
)
U
4 x 10
4 x 25
4 x 50
4 x 70
V
W
N (When the
UPS connects
to a non-linear
load, increase
the
cross-sectional
area.)
Battery
input
Nominal discharge current (A)
66
132
197
263
Maximum discharge current (A)
79
158
236
315
Recommended
cross-sectional
area (mm
2
)
+
3 x 16
3 x 50
3 x 70
3 x 120
N
–
Ground
cable
Recommended
cross-sectional
area (mm
2
)
PE
10
16
35
50
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
When the external conditions change, for example, the cable layout or ambient
temperatures, perform verification in accordance with the IEC-60364-5-52 or the local
regulations.
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is 415 V,
multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional areas of the
neutral wires 1.5–1.7 times.
The nominal battery discharge current refers to the current of forty 12 V batteries at 480
V in standard configuration.