UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
3 Installation
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
63
3.2.5 Routing Cables
3.2.5.1 Routing Cables from the Top
Context
Before connecting cables, ensure that the switches inside the UPS, the upstream input
switch and battery string switch are OFF to prevent operations with power on.
Route cables for the UPS from inside out and from bottom up.
Procedure
Step 1
Ensure the maintenance bypass switch is OFF. Open the front door, remove the front cover,
and remove covers from the top of the cabinet based on the site requirements.
Figure 3-22
Removing the cover