UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
3 Installation
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
73
Figure 3-35
Removing large covers
The quantity of holes in the above figure is for reference only.
If holes are drilled for routing cables, attach grommet strips on the hole edges to protect cables.
Step 11
Connect ground cables and power cables.
For the screw specifications and torque used for connecting cables in a bottom cable routing scenario,
refer to the top cable routing scenario. This section only shows the cable routes in the bottom cable
routing scenario.