Figure 3-38
Signal cable
The number and colors of signal cables are for reference only.
Step 14
Install the right cover of the UPS cabinet on the right of the cable entry cabinet, and install
other covers in the original positions.
----End
3.2.6 Remote EPO
Huawei does not provide the EPO switch or cable. If the cable is required, the
recommended cable is 22 AWG.
Equip the EPO switch with a protective cover to prevent misoperations, and cover the
cable with protective tubing.
Triggering EPO will shut down the rectifier, inverter, charger, and static bypass, but does
not disconnect the UPS mains input. To power off the UPS completely, open the front-end
input switch when triggering EPO.
Connect the requisite EPO switch to UPS dry contacts.