UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
5 Operations
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
139
Figure 5-2
Setting the Internet options
Step 3
In the address box of the browser, enter https://
UPS IP address
.
Step 4
Enter the correct user name and password and click
Login
.
Step 5
On the home page of the WebUI, choose
Monitoring
>
UPS System > Running Control
,
click
Inv. ON
, and confirm the operation to start the inverter.
Figure 5-3
Starting the inverter
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.
----End
5.1.4 Powering On Loads
Context
After the inverter starts, the UPS works in normal mode. The
Bypass mode
alarm disappears.