UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
8 Technical Specifications
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
165
Item
Specifications
Input mode
The mains input and bypass input share a power source or
use different power sources
8.7 Battery Electrical Specifications
Item
Specifications
Number of batteries
The UPS supports 30–44 batteries (40 by default). 34
batteries, the output power is derated to 94%. 32 and
30 batteries, the output power is derated to 80%.
Cold start
In the case of a mains failure, batteries can start the
UPS to power loads.
Charger output power
(6250 W±200 W) x N. The maximum charge power of
a power module is 6250 W±200 W (the maximum
current is 10 A). N represents the number of power
modules in the rack.
Charge voltage
Equalized charging voltage: 2.3–2.4 V/cell, 2.35
V/cell by default (30–42 batteries); 2.3–2.35 V/cell,
2.35 V/cell by default (44 batteries)
Float voltage: 2.23–2.3 V/cell, default: 2.25 V/cell
(30–44 batteries)
8.8 Output Electrical Specifications
Item
Specifications
Output system
Three-phase, four-wire, and PE
Voltage
380 V AC, 400 V AC, or 415 V AC (tolerance ±1%)
(line voltage)
THDv
THDv ≤ 1% (full linear load)
THDv ≤ 3% (full non-linear load)
Output PF
1
Transfer time
0 ms (uninterruptible transfer)
≤ 20 ms (interruptible transfer)
Output voltage unbalance
Voltage unbalance: ±3%, phase unbalance: 120±2°
Overload capability
Inverter overload capability: