7
Battery Specifications
Number of Battery Strings
Connected in Parallel to the UPS
Battery Capacity
9 Ah/12 V
2
9 Ah + 9 Ah = 18 Ah
9 Ah/12 V
3
9 Ah + 9 Ah + 9 Ah = 27 Ah
9 Ah/12 V
4
9 Ah + 9 Ah + 9 Ah + 9 Ah = 36 Ah
Starting the Inverter
6.2
a) Set parameters on the
Settings Wizard
screen. During setting, the
Bypass mode
and
No
battery
alarms do not need handling if they are triggered.
•
Single/Parallel
,
Output frequency
,
Battery
capacity
, and
Number of cells
must be
correctly set. Otherwise, the UPS running will
be affected.
•
Output voltage level
refers to the line voltage.
Initial Startup
b) View the system running status diagram on the MDU to check that the UPS is working in
bypass mode.
c) Start the inverter on the app.
• If you do not need to use the app to start the inverter, choose
System Info
>
Maintenance
>
Inv. ON
on the MDU.
• The
Service Expert
app can be downloaded from Google Play and can run on Android.
• The port number is
443
by default and can be modified. If the UPS is managed using the app,
the port number must be set to
443
.
NOTE