4 LCD and WebUI
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
98
Item
Description
Default Value Value Range
Cell float volt.
Indicates the battery float
charging voltage. The parameter
is configurable in any mode.
2.25 V/cell
2.23 V/cell–2.30
V/cell
Flt. volt. comp.
Option to correct the float
voltage based on the battery
temperature when a battery
temperature sensor is connected.
The value is configurable in any
mode.
Enabled
Disable, Enable
Temp. comp.
coef.
Coefficient for correcting the
float voltage based on the battery
temperature when a battery
temperature sensor is connected.
3.3 mV/°C*cell
0.0
mV/°C*cell–6.0
mV/°C*cell
Temp. comp.
center
Basic point of temperature
compensation.
25 °C
20–30
Discharge
Figure 4-23
Discharge screen
Item
Description
Default Value Value Range
Max. dis. time
Indicates the maximum battery
discharge time. When the
discharge time reaches the value,
the UPS powers off.
24h
16h–48h
Shallow Discharge Test