UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
4 LCD and WebUI
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
107
Item
Description
Default Value Value Range
hibernate
enable parallel hibernation to
alternate modules in hibernation
mode, which can prolong their
service life and improve the
system efficiency.
Module cycle
hiber. period
(d)
Indicates the rotation interval of
modules in hibernation mode.
The default value is 30, which
means that the hibernating
module is rotated every 30 days.
30
1–100
D.G. ECO
bypass supply
Indicates whether ECO bypass is
allowed to supply power in D.G.
mode. When the D.G. is
connected to the dry contact
signal GEN:
If this parameter is set to
Enable
, the system can enter
ECO bypass mode when the
D.G. supplies power to the
bypass and the ECO function
is enabled.
If this parameter is set to
Disable
, the system is not
allowed to enter ECO mode
when the D.G. supplies power
to the bypass.
Enable
Disable, Enable
RAM
verification
Enable or disable the memory
check function. If this parameter
is set to
Enable
, the control chip
RAM working status is checked
regularly. If this parameter is set
to
Disable
, regular check is
disabled.
Disable
Disable, Enable
Collect
real-time site
waveform
If this parameter is set to
Enable
,
one waveform can be stored
manually.
Disable
Disable, Enable
BCB trips in
case of EOD
If this parameter is set to
Enable
,
the BCB will trip in case of
EOD.
Enable
Disable, Enable
Input Setting
Item
Description
Default Value Value Range
D.G. mode
Set this parameter to
Enable
when a D.G. connects to the
input PDC. The UPS enters the
Disable
Disable, Enable