UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
5 Operations
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
134
Figure 5-3
WebUI login
e.
On the home page, choose
Monitoring
>
Control
. Click
Inv. ON
. In the displayed
dialog box, click
OK
to start the inverter.
Figure 5-4
Starting the inverter
If the power module receives a startup command when it cannot be started, it will retain the startup
command for 1 minute. Within 1 minute, if there is no situation (for example, the power module
encounters other faults or performs a shutdown command, or a fault is rectified) that requires the startup
command to be cleared and the power module becomes able to start, then the power module responds to
the startup command.
Step 6
Check that the UPS has transferred to normal mode by viewing the system running diagram.
Check on the LCD.
Check the UPS three-phase output voltage and frequency by choosing
Status
>
UPS
Output
to view real-time data on the LCD. Use a multimeter to measure the valid
three-phase output voltage and frequency.
Check on the WebUI.
On the home page, choose
Monitoring
>
Real-time Data
. In the
Output
area, check the
UPS three-phase output voltage and frequency.
If the displayed voltages are incorrect, choose
Maint.
>
Calib.
on the WebUI and expand
Power module
. Enter the measured voltages for
Ph. A output volt.
,
Ph. B output volt.
,
and
Ph. C output volt.
under
Actual Value
and click
Submit
at the end of each row to
commission the voltages.