UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
3 Installation
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
44
UPS
Capacity
Component
Specifications
Fixed value
50 kVA
Mains input circuit breaker
160 A/3P
136 A
Bypass input circuit breaker
125 A/3P
107 A
Output branch circuit
breaker
125 A/3P
107 A
75 kVA
Mains input circuit breaker
250 A/3P
213 A
Bypass input circuit breaker
250 A/3P
213 A
Output branch circuit
breaker
250 A/3P
213 A
The upstream input and downstream output circuit breakers recommended in
reference only.
If multiple loads are connected, specifications for branch circuit breakers must not exceed the
recommended specifications.
The circuit breaker selection principle is to protect loads and cables, and the cascading principle is to
realize specific protection.
3.1.4 Transportation and Unpacking
Prerequisites
Only trained personnel are allowed to move the equipment. Transport the UPS box secured
to a wooden support to the installation position using a pallet truck.
To prevent the UPS from toppling, secure it to the pallet truck using ropes before moving
it.
Move the cabinet with caution to avoid bumping or toppling, which may damage the
equipment. To avoid damaging the equipment, exercise caution while removing the
packing materials. Keep the UPS steady during unpacking.
If the UPS installation environment is poor, to well store the UPS after it is unpacked, take
measures to prevent dust. You are advised to wrap the UPS with the original plastic coat.
Procedure
Step 1
Verify that the UPS packing case is not damaged. If any damage is found, report it to the
carrier immediately.
Step 2
Transport the UPS to the specified position using a pallet truck.