UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
4 User Interface
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
114
Set an Ethernet IP address that ranges from 1.0.0.0 to 223.255.255.255. The default value
is
192.168.0.10
.
Ensure that the UPS IP address is unique on the network segment. Otherwise, the WebUI and
LCD display function may be abnormal.
Subnet mask
Set an Ethernet subnet mask that ranges from 0.0.0.0 to 255.255.255.255. The default
value is
255.255.255.0
.
Gateway
Set an Ethernet gateway that ranges from 1.0.0.0 to 223.255.255.255. The default value
is
192.168.0.1
.
RS485 baud rate/RS485 address
Set an address that ranges from 1 to 254 for this port.
Baud rate
depends on the network
management conditions.
Batt. temp. sensors
A maximum of four battery temperature sensors can be cascaded.
Start addr. of batt. temp. sensor
Set the DIP switch on the battery temperature sensor. Ensure that the addresses that you
set on the LCD are the same as the DIP switch addresses. Otherwise, communication
fails.
BMUs
BMUs can be cascaded. A maximum of 12 BMUs can be cascaded.
BMU start address
Set the BMU start address through the DIP switch on the BMU to 112. Ensure that the
address set on the MDU is consistent with that set for the DIP switch. Otherwise,
communication cannot be implemented.
Amb. temp. & humid sensors / Start addr. of amb. temp. & hum. sensors
The ambient temperature and humidity sensor looks the same as the battery temperature
sensor. The difference is that the former has a DIP switch address range of 32 to 44.
Therefore, you can use the sensor as an ambient temperature and humidity sensor or a
battery temperature sensor by setting the DIP switch address.
NTC
The short-distance battery temperature sensor monitors the ambient temperature near
batteries. It ensures that batteries work reliably and securely. The default status is
Disable
. If a short-distance battery temperature sensor is configured, set
NTC
to
Enable
.
Basic Param.