UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
4 User Interface
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
117
Figure 4-33
Advanced Param. screen 3
Figure 4-34
Advanced Param. screen 4
System capacity (kVA)
Rated system capacity, equals to capacity of each power module multiplied by the
number of requisite power modules. The
Module quantity mismatch
alarm will be
generated if the setting is incorrect.
Power module capacity (kVA)
Rated power module capacity.
Requisite modules
Matches the rated system capacity.
Redundant modules
Set in accordance with load capacity and redundant requirements.
Working mode
The value can be
Normal mode
(default),
Converter mode
,
Self-load mode
, or
ECO
.
BSC mode
−
The value can be
Non-BSC mode
(default) or
BSC mode
. The latter is set when the
system is a dual-bus system.