UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
4 User Interface
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
129
Figure 4-49
Dry Contacts screen 7
MUE05A connection
MUE05A connection status. Independent input signals can be enabled only when this
parameter is set to
Enable
.
Batter ground fault [BTG]
Enable or disable the battery grounding failure detection.
D.G. connection [GEN]
Enable or disable D.G. connection detection.
BCB connection [OL]
Enable or disable BCB connection detection.
Batter breaker [STA]
Enable or disable battery circuit breaker monitoring.
PDC output breaker [OUT]
Enable or disable PDC output circuit breaker monitoring.
PDC maintenance breaker [MT]
Enable or disable PDC maintenance circuit breaker monitoring.
BP/SYSMT Switch
If the BP/SYSMT switch is set to
Enable
, the port has dry contact signal access. How a
user uses the port depends on the status of the BP/SYSMT switch.
BP/SYSMT switch function
If the BP/SYSMT switch is set to
Enable
, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU bypass input switch or system maintenance switch.
SPD/SYSOUT Switch
If the SPD/SYSOUT switch is set to
Enable
, the port has dry contact signal access. How
a user uses the port depends on the status of the SPD/SYSOUT switch.
SPD/SYSOUT switch function
If the SPD/SYSOUT switch is set to
Enable
, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU input surge protector or system output switch.
MUE06A connection