UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
154
Figure 5-6
System Param. screen 1
Battery parameter settings have great impact on battery maintenance, battery lifespan, and
UPS discharge time. When you set battery parameters, note the following:
Set
Battery capacity
after repeated confirmation. An incorrect setting reduces the
charging power.
When a battery string is shared, the battery capacity of each UPS is the total capacity of
battery strings; when no battery string is shared, the battery capacity of each UPS is the
battery capacity of the single UPS.
A high or low charging power tends to shorten the battery lifespan, or even damages
batteries. To seek help about how to determine the battery capacity, contact Huawei
technical support.
Number of cells
refers to the number of 2 V cells in a single battery string connected to
the UPS, and the number of cells must be a multiple of 12 (for example, 180 and 192). For
example, if 36 batteries (150 Ah, 12 V) are connected in series to form a battery string, and
two of such battery strings are connected in parallel and then to the UPS, set
Number of
cells
to
216
(36 x 6) and
Battery capacity
to
300 Ah
(150 Ah + 150 Ah). If 192 batteries
(300 Ah, 2 V) are connected in series to form a battery string, and two of such battery
strings connected in parallel and then to the UPS, set
Number of cells
to
192
(192 x 1) and
Battery capacity
to
600 Ah
(300 Ah + 300 Ah). It affects the charge voltage and discharge
time. An incorrect setting will cause a high or low charge voltage, which greatly shortens
the battery lifespan. In addition, the UPS may shut down before the batteries are fully
discharged, which may lead to a data backup fault.