UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
159
Figure 5-14
AC Output screen
Check on the WebUI.
On the home page, choose
Monitoring
>
Real-time Data
. In the
Output
area, check the
UPS three-phase output voltage and frequency.
Figure 5-15
Real-time Data page
If the measured voltages are not within the normal ranges, choose
Maint.
>
Calib.
on the
WebUI and expand
Power unit
. Enter the measured voltages in
Ph. A output volt.
,
Ph. B
output volt.
, and
Ph. C output volt.
under
Actual Value
, and click
Submit
to commission
the voltages.