UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
166
5.1.5 Setting ECO Mode
Context
The UPS is set to non-ECO mode by default. Set the UPS to ECO mode when energy
saving is required.
When the UPS works in ECO mode, the bypass module takes precedence over the power
module in supplying power to loads. When the bypass module is disconnected, the UPS
switches to the power module. The switchover time is less than 2 ms for typical working
conditions and is 10 ms under harsh working conditions.
Both a single UPS and the parallel system support the ECO mode for higher efficiency.
To avoid frequent transfer between ECO mode and normal mode, do not set the ECO
mode when the bypass input is unstable or is sensitive to load changes.
ECO mode is not recommended when the load is less than 10%.
Before transferring the UPS to ECO mode, ensure that the bypass module works
properly.
Procedure
Step 1
Manually shut down the inverter to transfer the UPS to bypass mode.
Step 2
Select a value (
±5%
,
±6%
,
±7%
,
±8%
,
±9%
, or
±10%
) from the
ECO voltage range
drop-
down list box.
Figure 5-23
Setting ECO voltage range
Step 3
Set
Working mode
to
ECO
. Information indicating that the UPS works in ECO mode is
displayed on the LCD.