5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
183
In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and
the D.G. runs for 15 minutes), the signal for shutting down the D.G. is triggered.
If the battery voltage is greater than
D.G. startup batt. volt.
, the UPS exits intelligent power mode
and triggers the D.G. shutdown signal. If the battery voltage is less than
D.G. startup batt. volt.
, a
dialog box is displayed, indicating potential risks. Tap
OK
to exit intelligent power mode.
When disconnecting the D.G. from the UPS, set
Intelligent power
to
Disable
. Then the system will
automatically modify the following parameters:
Working mode
is set to
Normal mode
;
Intra-rack
power module start delay (s)
is set to
5
;
Output freq. track rate (Hz/s)
is set to
0.6
;
Input
adaptability
is set to
Weak
;
D.G. mode
is set to
Disable
; and
D.G. connection [GEN]
is set to
Disable
. You can modify these parameters as required.
----End
5.3.2 WebUI
Procedure
Step 1
On the login page, enter a user name and password, and click
Login
.
Step 2
Choose
Monitoring
>
Param. Settings
. Under
Intelligent Power Settings
, set
Intelligent
power
to
Enable
Figure 5-48
Intelligent power parameters on the WebUI
Intelligent power
The value can be
Enable
or
Disable
. The intelligent power function is available only if
the value is
Enable
. The default value is
Disable
.
ATS
The value can be
Connected
or
Not connected
. When the value is
Connected
, the UPS
works in the ATS scenario; when the value is
Not connected
, the UPS works in the
reused scenario. The default value is
Connected
. This parameter is available only after
you set
Intelligent power
to
Enable
.
D.G. startup batt. volt. (V/cell)
The value ranges from
1.80
to
2.00
. The default value is
1.80
. This parameter is available
only after you set
Intelligent power
to
Enable
.