UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
8 Technical Specifications
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
199
Item
360 kVA
400 kVA
440 kVA
480 kVA
75% load: 65 dB
50% load: 60 dB
8.3 Safety Regulations and EMC
Safety
Regulations/
EMC
360 kVA
400 kVA
440 kVA
480 kVA
Safety
regulations
EN62040-1: 2008
IEC62040-1: 2008
YD/T2165: 2010
GB/T14715-93
EMC
EN62040-2
IEC62040-2
IEC61000-2-2
IEC61000-4-2
EN61000-4-3
IEC61000-4-4
IEC61000-4-5
EN61000-4-6
IEC61000-4-8
8.4 Mains Input Electrical Specifications
Mains Input
Specifications
360 kVA
400 kVA
440 kVA
480 kVA
Input format
Three-phase, four-wire, and PE wire
Rated input voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input voltage range
138–485 V AC (line voltage)
The UPS5000-E power is not derated at 305–485V AC and is
linearly derated at 305–138 V AC
Rated frequency
50 Hz or 60 Hz
Input frequency
range
40–70 Hz