UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
8 Technical Specifications
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
201
In monitoring and power versions earlier than V100R001C10SPC008 (software package version:
V100R001C10SPC700), the battery voltage is 360-480 V DC (30 to 40 batteries, 32 by default).
8.7 Output Electrical Specifications
Item
360 kVA
400 kVA
440 kVA
480 kVA
Output system
Three-phase, four-wire, and PE
Voltage
380 V AC, 400 V AC, or 415 V AC (tolerance ±1%) (line voltage)
Frequency
In normal mode, the mains frequency is synchronized with the
bypass input frequency. In battery mode, the frequency is 50 Hz or
60 Hz (tolerance ± 0.25%)
Total harmonic
distortion of output
voltage (THDv)
< 1% (full linear load)
< 3% (full non-linear load)
Output power
factor
1
Transfer time
0 ms
Output voltage
unbalance
Voltage unbalance: ±3%; phase unbalance: ±2°
Overload capability Inverter overload capability:
105% < load ≤ 110%: transfer to bypass mode after 60 min
110% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
Bypass overload capability:
Load ≤ 135%: run continuously at 30°C or lower
1000% load: run for 100 ms
8.8 System Electrical Specifications
System
Specifications
360 kVA
400 kVA
440 kVA
480 kVA
Number of the
parallel UPSs
≤ 4
Power supply
reliability
The auxiliary power supplies, centralized controllers, and parallel
signals use a redundancy design
ECO
Supported