UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
B Alarm List
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
220
B
Alarm List
Alarm ID
(Alarm ID-
Cause ID)
Alarm Name Severity
Cause
Solution
0001-1
Mains voltage
abnormal
Minor
Cable connections
are incorrect.
The mains is not
normal.
The power module
is faulty.
The output or
battery is
incorrectly
grounded.
1.
Check whether cables to mains
are disconnected, loose, or
incorrectly connected.
2.
If cable connections are correct,
measure the mains voltage with a
multimeter. If the mains voltage
exceeds 280 V, the mains input
is not normal; if the mains
voltage is less than 272 V, the
sampling circuit of the power
module is not normal. Replace
the faulty module.
3.
Check whether the output or
battery is incorrectly grounded.
0001-2
Cable connections
are incorrect.
The mains is not
normal.
The mains input
fuse for the power
module is blown.
1.
Check whether cables to mains
are disconnected, loose, or
incorrectly connected.
2.
If cable connections are correct,
measure the mains voltage with a
multimeter. If the mains voltage
is less than 80 V, the mains
voltage is not normal; if the
mains voltage exceeds 88 V, the
power module sampling circuit
or fuse may not be working
properly. Replace the faulty
module.
0001-3
The mains is not
normal.
Check the mains.
0004-1
Mains ph.
Reversed
Minor
Cable connections are
incorrect.
Verify the cable connections.