UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
B Alarm List
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
223
Alarm ID
(Alarm ID-
Cause ID)
Alarm Name Severity
Cause
Solution
alarm is cleared. If the alarm
persists, the dry contact board
may be faulty. Replace the
board.
0032-1
Battery
overvoltage
protection
Critical
The battery voltage
is greater than the
upper threshold.
The configured
number of batteries
is less than the
actual number.
The actual number
of batteries does
not meet
requirements.
1.
Check the battery voltage.
2.
Check that the configured
number of batteries matches the
actual number.
3.
Check that the actual number of
batteries meets requirements.
0036-2
Battery
maintenance
reminder
Warning
The time for
maintenance arrives.
Maintain the batteries.
0037-1
Battery
undervoltage
Critical
The UPS has
worked in battery
mode for an
extended amount of
time.
The charger is
faulty.
1.
Check whether the battery
voltage is normal.
2.
Check whether the output is
overloaded.
3.
Check whether any battery is
damaged. If yes, replace the
battery.
4.
Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.
0040-7
Rectifier
abnormal
Critical
The fan for the
power module is
not functioning
properly.
The air channel for
the power module
is obstructed.
1.
Check that the air channel for the
module is free from blockage.
2.
Check whether the fans are
functioning properly. Replace the
power module if the fans are
faulty.
0043-1
Fan abnormal
Critical
The fan for the
power module is
abnormal.
The fan monitoring
cable for the power
module is not
working properly.
Replace the faulty power module.
0043-2
The fan is faulty.
Check the fan or replace the bypass
module.
0043-3
The fan is faulty.
1.
Replace the fan.