UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
B Alarm List
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
226
Alarm ID
(Alarm ID-
Cause ID)
Alarm Name Severity
Cause
Solution
is broken.
0085-1
EPO
Critical
The EPO button is
pressed.
Restore the EPO button status. Start
the UPS after the alarm is cleared.
0086-1
Max. number
of BPM
transfers
Minor
The system frequently
transfers to bypass
mode due to overload
timeout or load
impact.
Check the load.
0087-1
System
transfer-to-
bypass
Warning
The neighboring UPS
is not normal, and
transfers to bypass
mode.
Check the reason why the
neighboring UPS transfers to bypass
mode.
0088-1
Rack address
conflict
Critical
The configured rack
address conflicts with
another one.
Check the rack address setting.
0089-1
Rack output
overload
Minor
The load is
excessive.
The rack capacity
setting is not
appropriate.
Check the load and remove some
loads or expand the UPS power
capacity if the UPS is
overloaded.
Check that the configured rack
capacity meets requirements.
0090-1
Dry contact
board fault
Critical
I2C communication
with the dry contact
board MUE05A fails.
Replace the dry contact board
MUE05A.
0090-2
I2C communication
with the dry contact
board MUE06A fails.
Replace the dry contact board
MUE06A.
0356
Battery Mode
Minor
The UPS is working in
battery mode.
The running status is displayed. See
details about how to handle other
alarms.
0359
No power
supplied
Warning
No power is supplied.
The running status is displayed. See
details about how to handle other
alarms.
0332
Output
disabled
Minor
The output is disabled.
The running status is displayed. See
details about how to handle other
alarms.
0337
PDC bypass
input breaker
open
Critical
The bypass input
circuit breaker on the
PDC is OFF.
The running status is displayed. No
further measures are required.
0338
PDC output
breaker open
Critical
The output circuit
breaker on the PDC is
OFF.
1.
Check that all UPS output circuit
breakers are ON.