UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
B Alarm List
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
227
Alarm ID
(Alarm ID-
Cause ID)
Alarm Name Severity
Cause
Solution
2.
On the LCD, check that
PDC
output breaker open
alarm has
disappeared. If the alarm persists,
tap the
Clear Fault
button to
clear the alarm.
0341
PDC Maint.
breaker closed
Minor
The maintenance
circuit breaker on the
PDC is ON.
The running status is displayed. No
further measures are required.
0342
Mains input
breaker open
Critical
The mains input circuit
breaker is OFF.
The running status is displayed. No
further measures are required.
0343
BPM input
breaker open
Critical
The bypass input
circuit breaker is OFF.
The running status is displayed. No
further measures are required.
0340
Maint.
breaker closed
Minor
The maintenance
circuit breaker is ON.
The running status is displayed. No
further measures are required.
0335
Generator
connected
Warning
The generator is
connected.
The running status is displayed. No
further measures are required.
0594-1
Insufficient
redundant
racks
Minor
The load is
excessive.
The configured
number of
redundant racks is
incorrect.
1.
Reduce the load.
2.
Decrease the configured number
of redundant racks.
0095-1
Insuffi.
redundancy
Minor
The load is
excessive.
The configured
number of
redundant modules
is incorrect.
1.
Reduce the load.
2.
Decrease the configured number
of redundant modules.
0096-1
ECO volt.
Abnormal
Minor
The ECO bypass
voltage or
frequency is out of
the preset range.
The ECO bypass
voltage or
frequency range is
incorrectly set.
The bypass input
sequence is reverse
or the neutral wire
is disconnected.
1.
Check the bypass input voltage
and frequency.
2.
Check that the rated voltage,
rated frequency, ECO bypass
voltage range, and frequency
range are correctly set.
3.
Check that the bypass cables and
circuit breakers are correctly
connected.
0098-1
Bypass
current not
shared
Minor
The output and
input circuit
breakers are OFF.
1.
Check that the output and bypass
input circuit breakers on each
rack are ON.